33
a Compact Flash data card in real time, then rearm and be ready to
capture data during the next test run.
Fault Recorder: A fault in a wire circuit is usually due to unintentional
grounding, a break in the line, a crossing or shorting of the wires, etc. A
digital fault recorder logs extended duration cycle-by-cycle recording.
Under the fault recorder mode, triggers are voltage-based. PX5 can help
locate failures detected in various components of assorted equipment by
recording an extended period of cycle-by-cycle data to capture the entire
duration of the fault and the associated system response.
Long-term Timed Recording, Demand, Energy: Performing a statistically
valid power quality energy survey requires the capture of a set of basic
data over an extended period of time. PX5 is designed to facilitate long-
term monitoring by collecting min/max/avg data at each predetermined
interval in order to perform post-process harmonic and other events
analysis. PX5 is also designed to be left unattended in the field,
recording statistically representative data for long-term analysis. Using
the Dranetz lockable portable case option or other available enclosures,
power quality studies can be carried out in harsh weather environments.
Continuous Data Logging, Demand, Energy: This logs the rms and
power values once per second for totally gapless logging. Cyclic triggers
are disabled. No waveforms are recorded under this monitoring mode.
EN50160 Power Quality: EN50160 monitors and reports Quality of
Supply (QOS) compliance as specified by the EN standard. The seven
parameters required by EN50160 to determine QOS compliance are:
Power Frequency, Supply Voltage
Variations, Rapid Voltage Changes, Supply Voltage Unbalance,
Harmonic Voltage, Interharmonic Voltage, and Mains Signalling.
Motor Quality: Automatically sets up the parameters that affect the
operation of motors. Motor parameters include True Power Factor,
Horsepower, and Derating Factor, among others.