Example of Power Quality setup using the Wizard
Current Probe
Select the current probes you are going to use from the list. If you are
using LEMFlex make sure the probe and list match exactly. Full scale
current should not exceed probe rating and nominal current should not
be less than 10% of full scale.
Scale Factors
Set Scale factors if working with the secondary of PTs or CTs. If your
Probe is in the list and selected, Amps Scale Factor should be 1 if not
connected to a secondary of another CT.
Circuit Type
Select the circuit type. If you see a mismatch while connected you may
not be connected properly or your current probes are reading <10% of
full scale or could be V or I imbalance. You can choose to override and
monitor anyway although not recommended if connection is wrong.
Nominal Values
If connected the unit will show values it is reading. If you are not
connected, then you can set your values by pressing the blue bordered
box.
Mode of Operation
Select Continue
Monitoring Mode
Select Standard Power Quality
Advanced Options
Six Sub-categories
1) Transient – Leave defaults as long as Nominal Values were
correct.
2) RMS Variation – Leave defaults as long as Nominal Values were
correct.
3) Waveform Capture – Easiest thing to do is set all boxes with a
check mark.
4) Characterizer Options – Verify IEEE 1159.
5) Journal Limit – Select Disable, then disable All
Note that this will disable alarming functions on the annunicator
panel status report. Activate only those that you specifically
need.
6) Journal Interval – Leave defaults.